This program provides calculation procedures necessary to perform complete design and analysis of a propped-cantilevered retaining wall.

 

The retaining wall may be loaded with any of the following load combinations :

Any angle of sloped backfill.
Surcharge loading above heel or toe.
Eccentric axial dead and live load on stem.
Lateral and vertical load from an adjacent footing.
Wind or seismic force on projecting portion of stem.
An additional uniform lateral load may be applied to the wall.

 

The following overall dimensions can be specified:

Retained height and top support height
Toe and heel dimension.
Wall extension above retained height.
Footing key depth, width, and location.
Soil height over the toe.

 

The following stability checks are performed:

Total overturning and resisting moment.
Optional Inclusion of vertical active pressure on the rear face of the wall to resist overturning.
Sliding resistance using both passive and active pressure.
Both heel and toe of the footing are designed as follows:
Toe Design - Find actual moment at stem face, check required minimum reinforcing, list rebar choices, and check one-way shear.
Heel Design - Find moment at stem face, check required minimum reinforcing, list rebar choices and check one-way shear. User may neglect upward soil pressure for conservative design.

 

 

 

clip0386

 

 

 

 

Basic Usage

Entering Soil Data specifies the lateral earth pressures applied to the wall. Active Pressure will be used on over toe and/or heel unless Slope is non-zero. If this is the case, then the soil is sloped and Slope Pressure will be used behind the wall to generate lateral loads. Maximum Pressure can be entered to instruct the program to limit the lateral pressure intensity. (The pressure diagram then becomes uniform). Passive Pressure will be used for the full depth of soil in front of the wall to resist sliding. Soil Density will be used for soil weight, and Soil Height Over Toe will be used to define passive pressure height, vertical load, and will create an active pressure resisting overturning.
You can apply two additional vertical Loads: an Axial Load to the top of the stem (with optional eccentricity), and Toe and Heel Surcharges. If the heel surcharge is permanent, you can specify that it Should Be Used To Resist Overturning.
In addition to the lateral loads created by the soil above the footing, you can apply additional Lateral Loads to the wall. Enter a Lateral Loads Acting on the Stem Above Soil when your wall will extend above the soil, such as a screen or guard wall. Impact and bracing loads can be applied to the wall using the Additional Lateral Load item, letting you specify a load intensity and length. You can also enter an Adjacent Footing Load, by specifying the magnitude of load and position relative to the rear of the topmost stem section.
The Wall and Footing Data section is used to specify the retained height, stem height above soil, and footing dimensions. Zero entries are permitted for the key and either toe or heel width. While using the program, you can easily change these values often and recalculate [F9] to determine soil pressures, overturning stability, and sliding stability.
The critical footing wall design values are given in the Summary area, where you can review calculated results and then modify the wall and footing data as required.
The program will perform a Sliding Check when you enter Footing/Soil Friction coefficients, and can Neglect a certain height of soil, if the soil in front of the wall is non-compacted.
By simply entering the concrete strength, steel strength, and minimum steel percentage the program will provide a full Footing Analysis and Rebar List.
Stem Design can be performed for up to five independent sections of the wall. By specifying Wall Construction Type, Design Height, and Wall Thickness and Reinforcing, each stem section can be easily refined for an optimum design.
The Summary of Overturning and Resisting Moment table should be reviewed if you have any questions on how the vertical and lateral loads are being applied to the wall.
When you are satisfied with the wall, Print or Save the current worksheet, choose Reset to start another wall design, or use the Access Menu to choose another program.

 

 

Unique Features

Slope of backfill may be varied from flat to 45 degrees.
Either a concrete or masonry stem can be specified. When concrete is chosen, the wall thickness, rebar size, and location is used to calculate the minimum spacing for the rebar. When masonry is specified, the option of special inspection is entered in addition to the above values, and the maximum rebar spacing is calculated at 8" modules.
The program has the unique ability to design screen walls for conditions where the wall extends a distance above the soil which is much greater than the retained height.

 

Assumptions & Limitations

Both active and passive pressures are applied as Equivalent Fluid Pressures.
Friction coefficient is assumed to be applicable for both friction only and friction combined with passive pressure cases.
Design for bending reinforcement in Toe and/or Heel of footing is calculated using d = thickness minus 3".
If surcharge exists above the Toe or Heel, the soil height over those areas will be increased (internally) by the ratio of Surcharge/Soil Density.
All concrete design is based on ACI Ultimate Strength Design.

 

 

Example

The data entry for this example is shown in the screen captures that accompany the Data Entry Tabs and Results & Graphics Tabs sections to follow.

 

 

clip0388

 

 

Data Entry Tabs

This set of tabs provides entries for all input in this calculation. While you are entering data and switching between these tabs you can view the desired resulting information on the tabs on the right-hand side of the screen (calculated values, sketches, diagrams, etc.). A recalculation is performed after any entry data is changed. After each data entry you can view the results on the right-hand set of tabs.

 

 

General Data Tab

 

 

clip0389

                                                         

 

Retained Height

This is the height of retained earth measured from top of footing to the top of soil behind the stem (over the heel). When the backfill is sloped, the soil will slope away and upwards from this height. The actual retained height used for overturning and soil pressure calculations will be the retained height projected at the vertical plane of the back of the heel, but for stem moments, no such increase will be made. Using the spin-buttons you can vary this in 3-inch increments (you can type in any number). After each entry you can press the tab key to advance to the next entry, or use your mouse to position the cursor.

 

Wall Height Above Retained Soil

Use this entry to specify if the wall extends above the retained height. This entry is typically used to define a "screen wall" projection above the soil retained. This extension can be used as a weightless "Fence" or a concrete or masonry stem section without any soil retained behind it. You can enter wind load on this projection using the entry "Load @ stem above soil" on the "Loads" tab. We'll handle the fence when we get to the STEM design screen.

 

Height of Soil Over Toe

Measured from the top of footing to top of soil, this may vary from a few inches to a few feet (it is measured in inches) depending upon site conditions. It is used to calculate passive soil pressure depth (considering "Ht. to Neglect" on "Sliding" tab). This soil can also be used to calculate an active pressure to reduce overturning; this is a choice on the Options Screen, and can have significant effect if the footing is well below grade.

 

Water Table Height Over Footing

If you want to design for a water table condition, enter the maximum height from top of footing to water table level. The program will then compute the added pressures for saturated soil on the heel side of the footing, including buoyancy effect, to calculate increased moments and shears on the stem, and overturning. Do not enter a height greater than the retained height, nor a liquid other than water.

 

Soil Slope

You may enter any backfill slope behind the wall. Use the drop-down menu or type the slope ratio as Horiz/Vert. The soil must be level or slope upward. Negative backfill slopes (grade sloping downward, away from the wall) are not allowed.

 

The program will use this slope to 1) include the weight of a triangular wedge of soil over the heel as vertical load, and 2) compute overturning based upon an assumed vertical plane at the back face of the footing extending from the bottom of the footing to ground surface - a steeper slope will result in a higher overturning moment. We suggest not using a slope steeper than 1.5 to 1.0 unless approved by the geotechnical engineer. The program will not accept a backfill slope steeper than the angle of internal friction.

 

Allowable Soil Bearing

The maximum allowable soil bearing pressure for static conditions. Using the spin buttons you can increment in 50 psf steps. Usual values for this vary from 1,000 psf to 4,000 psf or more.

 

Lateral Pressure Method

Here you can choose between E.F.P. or Rankine formula or Coulomb formula. EFP means "Equivalent Fluid Pressure," where you can enter a lateral soil pressure in psf per foot of depth. "Rankine" or "Coulomb" instructs Retain Pro to use the Rankine or Coulomb Method to calculate active and passive soil pressures using an entered angle of internal friction for the soil. When Rankine or Coulomb is chosen, the Ka*Density value for active pressure is computed.

 

Active Soil Pressure - Heel Side (EFP Method Chosen)

Active Pressure: Ka * Gamma (Rankine or Coulomb Method Chosen)

Enter the equivalent fluid pressure (EFP), or the angle of internal friction if Rankine or Coulomb is chosen, for the soil being retained that acts to overturn and slide the wall toward the toe side. This pressure acts on the stem for stem section calculations, and on the total footing+wall+slope height for overall stability and soil pressure calculations.

 

Commonly used values, assuming an angle of internal friction of 34, are 30 pcf for a level backfill; 35 pcf for a 4:1 slope; 38 pcf for a 3:1 slope; 43 pcf for a 2:1 slope; and 55 pcf for a 1.5:1 slope. These values are usually provided by the geotechnical engineer. If the Rankine or Coulomb method had been chosen, these values will be computed using those formulas.

 

When the retained soil is sloped, a vertical component of the lateral earth pressure over the heel can be applied vertically downward in the plane of the back of the footing. You can choose to apply this force for overturning resistance, sliding resistance, and/or for soil pressure calculations, by checking the boxes on the CRITERIA > Option screen.

 

 

Angle of Internal Friction (Rankine or Coulomb Method Chosen)

This value is entered in degrees and is the angle of internal friction of the soil. This value is usually provided by a geotechnical engineer from soils tests, but can also be found in reference books or building codes for various typical soil classifications. This value is used along with Soil Density within the standard Rankine and Coulomb equations to determine "Ka" and "Kp" multipliers of density to give active and passive soil pressure values.

 

Active Soil Pressure - Toe Side

If the EFP method is chosen, enter the active pressure to be used on the toe side of the wall. This active pressure is used along with the "Soil Height over Toe" value (entered on the Sliding tab) to calculate a stabilizing soil force on the wall. This front side of the wall is assumed to be level.

 

When either the Rankine or Coulomb method is chosen, the angle of internal friction is used in the Rankine formula with an assumed level toe-side slope.

 

The active pressure from soil over the toe partially counteracts the heel-side active pressure for overturning calculations.

 

Passive Pressure  (EFP Method Chosen)

Passive Pressure: Kp * Gamma (Rankine or Coulomb Method Chosen)

This is the resistance of the soil in front of the wall to being pushed against to resist sliding. Its value is in psf per foot of depth (pcf). For the E.F.P. method, you input this value, which is usually obtained from the geotechnical engineer. If the Rankine or Coulomb method is chosen, it will be computed and entered for you. Its value usually varies from 100 pcf to about 350 pcf.

 

Soil Density

Enter the soil density for all earth above the toe and heel of the footing. This weight is used to calculate overturning resistance forces and soil pressures using the weight of the soil block over the projecting toe and heel of the footing. When surcharges are applied over the soil, the surcharges are transformed to equivalent uniform lateral loads acting on the wall by the ratio force = (Surcharge/ Density)*Lateral Load. Input this value in lbs. per cubic foot. Usual values are 110 pcf to 120 pcf.

 

Material Data Tab

This screen allows you to change properties of masonry and concrete. It also allows you to decide what load factor (1.4 or 1.7) to use for factored soil pressure attributable to dead loads.

 

clip0390

 

For Masonry

 

Concrete Block Type

This allows you to select Lightweight, Medium weight, or Normal weight concrete masonry units.

 

Factor Applied to _bm30 for Calculation of Em

The modulus of elasticity for masonry is 750 _bm31 (UBC '97 2106.12.1). This entry allows you to select a multiplier other than 750.

 

Multiplier Applied to Wall Weight from Tables

This entry allows you to increase or decrease the internal default values of stem weights, as displayed on the STEM screen.

 

For Concrete

 

Stem concrete weight

This is usually 145-150 pcf, but may be changed with this entry.

 

Footing concrete weight

This option is necessary since if there is any buoyancy effect, this will reduce the effective weight of the footing concrete.

 

ACI Factored Soil Pressure

This gives you two choices for computing the factored moment in the toe. Select either a 1.7 load factor for both dead load and pressure attributable to live load and lateral soil pressure on the wall. Alternatively, and less conservative, use a load factor of 1.4 for dead load (footing and superimposed earth) and 1.7 for live load and upward soil pressure attributable to lateral soil pressure.

 

Options Tab

This screen is critical to your design, since many subsequent calculation results will be affected. Review and check these boxes carefully.

 

 

clip0391

 

Slab is Present to Resist all Sliding Forces

Check this box when a slab is in front of the wall to resist lateral sliding. This negates sliding concerns (but check the slab if necessary). For restrained wall footings, it deletes the lateral force (base stem reaction) applied to the top of the footing, puts "not applicable" in the sliding ratio display, and dims the sliding entries on the FOOTING > KEY DIMENSIONS AND SLIDING sub-tab screen. The slab restraint is assumed to be at the top of the footing and the program does not allow it to be placed higher-if this condition occurs, append your printout with hand-calcs,

 

Use Toe Surcharge to Resist Sliding and Overturning

Checking this box will include the weight of soil overburden on the toe to resist overturning and add to its weight for frictional resistance.

 

Use Heel Surcharge to Resist Sliding and Overturning

Checking this box will include heel surcharge. If surcharge is live load and its use would be non-conservative, don't check this box.

 

Neglect Upward Pressure at Heel

For heel calculations you may choose to neglect the upward soil pressure, typically resulting in greater heel moment. If this box is checked the Mu for upward loads will be zero.

 

Toe Active Pressure Used

Checking this box will apply the toe side active pressure to reduce overturning moment and reduce sliding force to a net sliding force to be resisted.

 

Choices for Use of Vertical Component of Active Pressure

The vertical component of the lateral pressure is applied at a vertical plane at the back of the footing. You can optionally use this to resist overturning, sliding, or for soil pressure calculations. (For the latter it can make a considerable difference). Checking these boxes applies the options. For a level backfill, this option will back-solve the EFP method to find the equivalent internal friction angle, then apply this vertical component equal to tan. If either the Rankine or Coulomb method had been chosen, this vertical component would be tangent of _bm37.

 

Note that most texts suggest using the vertical component only to resist overturning. For a level backfill these options are usually not used.

 

 

Loads / Vertical Loads Tab

Additional loads on the wall are entered on these sub-tabs.

 

clip0392

 

Surcharge Over Toe

If other loads are imposed directly above the toe (such as a slab, storage, or moving load), these may be entered here (you have already entered the height of the soil over toe). This surcharge is divided by soil density and multiplied by active pressure to calculate an equivalent lateral load. This surcharge is used to calculate soil pressure. You can use this surcharge to resist sliding and overturning by clicking the box on the CRITERIA > Options sub-tab.

 

Surcharge Over Heel

This surcharge is considered uniformly applied to the top surface of the retained soil (over the heel). It may be entered whether or not the ground surface is sloped, but is always taken as a vertical force. This surcharge is divided by the soil density and multiplied by the Active Pressure to create a uniform lateral load applied to the wall. You can use this surcharge to resist sliding and overturning by clicking the box on the CRITERIA > Options sub-tab.

 

Axial Loads Applied to Top of Stem

These loads are considered uniform load along the length of the wall. They are applied to the top of the topmost stem section and effect the design of masonry stems only. The dead and live loads are used to calculate stem design values and factored soil reaction pressures used for footing design. Only the dead load is used to resist overturning and sliding of the retaining wall.

 

Axial Load Eccentricity

This is the eccentricity of the axial load with respect to the centerline of the uppermost stem section. The eccentricity moves the load toward the toe, causing bending moments that are additive to those caused by the lateral soil pressure over the heel (negative eccentricities are not accepted).

 

Adjacent Footing Load

This entry gives you the option of placing a footing adjacent and parallel to the back face of the wall, and have its effect on the wall included in both the vertical and horizontal forces on the wall and footing. Refer to the General Reference Diagram for locations where input measurements should be taken.

 

For a "Line Load" the load entered is the total load per foot parallel to the wall (not lbs. per sq. ft).

 

If the adjacent footing is specified as "Square Footing" (not line load), the load entered should be the adjacent footing load divided by its dimension parallel to the wall, giving a pounds per lineal foot value, as for a continuous (line) footing.

 

A Boussinesq analysis is used to calculate the vertical and lateral pressures acting on the stem and footing. The program uses an assumed Poisson ratio of 0.3. (See Foundation Analysis and Design, 5th Edition, by J. E. Bowles, McGraw-Hill, pages 629-639)

 

Use of the Adjacent Footing may not be applicable if the horizontal distance from back face to stem to closest edge of adjacent footing is greater than the distance from top of wall footing to bottom of Adjacent Footing (i.e. outside an assumed line of influence).

 

When the Boussinesq analysis is used, the program may require additional computing time, depending upon the speed of your computer. To avoid this delay (which occurs any time any entry is changed) we suggest you use a vertical load of zero until your data entry is nearly finalized. Then enter the actual footing load and modify your final values.

 

Suggestion: For adjacent truck or highway loading, it may be preferable to use a heel surcharge (uniform) of 250 psf (or more) instead of treating it as an "adjacent footing."

 

Do not use this feature if the adjacent footing load is farther from the stem than the retained height, less the depth of the adjacent footing below the retained height, since at this distance it will not have significant effect on the wall.

 

Footing Width

Width of the adjacent footing measured perpendicular to the wall. This is necessary to create a one-foot long by Width wide area over which the load is applied.

 

Footing Eccentricity

This entry is provided in case the soil pressure under the adjacent footing is not uniform. Enter the eccentricity of the resultant force under the adjacent footing from the centerline of the footing. Positive eccentricity is toward the toe, resulting in greater pressure at the side of the adjacent footing closest to the stem. The program will use the vertical load and eccentricity and create a trapezoidal pressure distribution under the adjacent footing for use with the Boussinesq analysis of vertical and lateral pressures.

 

Wall to Footing Centerline Distance

Distance from the center of the adjacent footing to the back face of the stem at the retained height.

 

Footing Type

This drop down menu selection allows you to enter either an isolated footing using the "Square Footing" selection, or a continuous footing using the "Line Load" selection.

 

Base Above/Below Soil at Back of Wall

Use this entry to locate the bottom of the footing with respect to the Retained Height. Entering a negative number places the footing below the soil. A positive entry would typically only be used when the soil is sloped and the footing resides "uphill". To insert a negative number, first type the number then press the "-" (minus) sign.

 

Note: If the "Adjacent Footing" is another retaining wall at a higher elevation, the Boussinesq analysis may be used for the vertical load applied to the soil from the wall, however the design must also consider the lateral (sliding) loads from that adjacent wall. This load could be applied as "Added Lateral Load", however this is at the discretion of the designer and is not within the scope of the program. Caution is urged for this condition. See discussion in the companion book: Basics of Retaining Wall Design.

 

 

Loads / Lateral Loads Tab

 

clip0393                        

Load @ Stem Above Soil

This load (typically a wind load) will be applied to that part of the stem projecting above the retained height defined by the entry "Wall height above retained soil." It is used to calculate overturning moment and shear, stem design moment and shear, and soil pressures. Customary values are 10 psf or higher. Only a positive "+" value can be entered (i.e., the force may only be applied in a direction to add overturning, in the direction of the active soil pressure).

 

Added Lateral Load

This input allows you to specify an additional uniformly distributed lateral load applied to the stem. You can use it to apply a seismic load to the wall, an additional uniform lateral load due to soil pressure, or apply a short but intense load due to impact of a car or similar force (this case can be modeled by separating the "Height to Bottom" and "Height to Top" by just one foot, and using an "Added Lateral Load" equal to the total added force). This load is factored by 1.7 to calculate concrete moments and shears.

 

Height to Top

This dimension defines the upper limit of the added lateral load measured from the top of the footing. Do not enter a dimension higher than the top of the wall ("retained height" plus "Wall height above retained soil").

 

Height to Bottom

This dimension defines the beginning (or bottom) of the added lateral load measured from the top of the footing.

 

 

Stem Tab

The layout of this screen will change depending upon whether you previously chose a conventional cantilevered wall, a tapered stem wall (earth side battered), or a gravity wall. This screen is for a straight stem non-battered wall.

 

clip0394

 

 

Wall Type

If Restrained Stem is selected, you may have a lateral support (such as an abutting roof, slab-on-grade over backfill, or tiebacks). The lateral support should be near the top of the wall, although some extension of the wall above the support is permitted. You have the option of fixing the base (as for a cantilevered wall) or assuming it pinned. Intermediate degrees of fixity are not permitted. The program will compute moments, shears, and stresses at three locations: base (negative moment if fixed; zero moment if pinned), maximum positive moment between base and support, and at the point of support.

 

Material

Select Masonry or Concrete. Only one material can be used, and must be of constant thickness.

 

Support Height

Use the spin buttons (or type the value) for height from base to level of support. To check the overall wall height that you had input (retained height plus height above soil) just click the CRITERIA tab.

 

Thickness

The program only permits a constant thickness throughout the height of the wall.

Use the spin button (or type) the choice for thickness. If Masonry was chosen, the drop down menu will give you modular choices.

 

Fix Stem @ Base

Clicking this box will check footing and stem for 100% fixity at base. If unchecked, pin condition will be assumed.

 

_bm113

Enter choice for masonry or concrete.

 

_bm115

Enter choice for masonry or concrete.

 

Rebar Cover

This appears if a concrete stem is chosen and lets you enter desired cover on toe and earth side.

 

Inspection

This is applicable to masonry stems only, and if checked, the full allowable _bm118 used in flexure, shear, and axial stress will be used. If not checked, the allowable values will be reduced by one-half. The Uniform Building Code requires this reduction if Special Inspection is not provided.

 

Solid Grout

This applies to masonry only, and if this box is checked the weight of the wall will be based upon industry standard solid-grout weight for either lightweight, medium weight, or normal weight. If this box is not checked, the program will calculate the weight based upon grouting of only cells containing reinforcing. This also affects equivalent solid thickness for stem shear calculations

 

Short Term

This is used for masonry design only, and indicates the allowable overstress multiplier (1.33 for wind and seismic). For a concrete wall this does not apply since strength design is use, and this entry should be 1.0.

 

Stem Design

This allows you to design or check wall moment and shear at three locations: @ Top Support, @ Mmax Between Ends, and @ Stem Base. If base is pinned, the entries under @ Stem Base will be zero or dimmed.

 

Ht. Above Footing

This displays, from left to right, the distance up to lateral support, height to point of maximum positive moment, and at the base of the stem.

 

Rebar Depth "d"

From the wall thickness and center/edge condition specified, the program will determine the "d" to be used for design (using the internal tables and default modifications). See Rebar Position, above. For concrete, the program will automatically add to cover chosen one-inch allowance for one-half bar diameter, for determining "d" to be used.

 

Rebar Size

Select from the drop-down menu.

 

Rebar Location

Click the button for Center or Edge.

 

Rebar Spacing

Enter your trial choice, or for masonry, select from the drop-down menu.

 

Actual Moment

This will show moments at the indicated locations with (+) and (-) as applicable. For concrete the moments will be factored by 1.7.

 

Allowable Moment

This will be calculated based upon the data you have entered. For concrete, it will be based upon strength design (factored by 1.7).

 

Status

This indicates whether your stem design is OK at the selected height or at the base or displays   Mu > Phi  Mn   or   As < min   or   As > max.

 

Rebar Lap Req'd Above / Below

For masonry, the lap required is 48 bar diameters for Fs = 24,000 psi and 40 diameters for Fs = 20,000 psi.

 

For concrete, a Class B splice is assumed, which multiplies the development length by 1.3 (See ACI 12.15.2), and excludes reduction for stress level.

 

Note: The program does not compute or display bar cut-off points, which must be done manually, or extend positive reinforcing so it is acceptable.

 

Shear at Section

This is the total shear at the indicated height (factored for concrete).

 

Actual Shear

Unit shear stress at designated height computed by area = 12  "d".

 

Allowable Shear

Based upon 0.85  2 _bm124 for concrete and _bm125 for masonry, reduced one-half for no inspection, and not to exceed 50 psi.

 

 

Footing Tab / Footing Dimensions

This is the screen where you design the footing, by manipulating the heel and toe widths so the actual soil pressure is less than allowable, or you can use the Automatic Footing Design button (described below) to size the footing. This screen also gives you choices for toe and heel reinforcing, or indicates if it is theoretically not required. It also suggests key reinforcing, if applicable.

 

 

clip0379

 

 

Toe Width

This is the width of the Toe of the footing, and is measured from the front edge of the footing to the front face of the stem. Can be set to 0.00 for a property line condition. All overturning and resisting moments are taken about the bottom-front edge of the toe.

 

Heel Width

Distance from front face of stem to back of heel projection. If a dimension is entered that is less than the stem width at the base, the program will automatically reset the heel dimension to at least the stem width. For a property line at the rear face of the stem, this dimension would be the stem width.

 

Total Footing Width

The calculated width of the footing, Toe Width + Heel Width.

 

Footing Thickness

Total footing thickness, NOT including the key depth (if used). For bending and shear design of the footing, the rebar depth "d" is taken as Footing Depth - Rebar Cover - ½" (to account for the rebar radius). If footing thickness is inadequate for shear capacity a red warning indicator will appear.

 

The footing thickness must be greater than the rebar embedment length required for the bottom stem reinforcing + rebar cover. If you enter a dimension less than required for stem bar embedment, a red message will appear at the top of the screen. The program adds the calculated hooked bar embedment from the STEM screen and adds it to the rebar cover you have chosen for the bottom of the footing (usually 3"). This will trigger the red warning. If inadequate thickness, increase the thickness, or change the stem dowels, until this message disappears.

 

Center Stem on Footing

Clicking this bar will adjust the toe and heel widths you have entered so stem is centered on the footing but overall width remains the same.

 

_bm131

Enter concrete compressive stress for footing.

 

Fy

Allowable rebar yields stress to be used for design of footing bending reinforcement.

 

Rebar Cover in Heel/Toe

Distance from the face of concrete to edge of rebar. The program will add 1/2" to this value and subtract the result from the footing thickness to determine the bending "d" distance.

 

Minimum As Rebar Ratio

Enter the absolute minimum steel percentage to be used to calculate rebar spacing requirements (0.0018 Ag for Fy=60,000 psi). If the % steel required by stress analysis is less that 200/Fy, the minimum of (200/Fy -or- 1.333 * bending percentage required) is calculated and compared with the Minimum As% entered here, and the greater of the two used to calculate rebar spacing requirements.

 

Rebar at Stem Base

This is a reminder of the size and spacing of the bottom stem reinforcing, to make it easier for you to select toe reinforcing to match (toe reinforcing is usually the bottom stem dowel bars bent toward the toe).

 

Toe Reinforcing Options

This list gives you choices for reinforcing sizes and spacing for the bottom toe bars. Typically the toe bars are extensions of the stem dowels, which are bent out toward the toe. Therefore, you will probably want only to verify that the stem dowel bar size and spacing do not exceed the selections offered.

 

Heel Reinforcing Options

This list gives you choices for acceptable sizes and spacing of top heel bars. It is desirable to select a spacing that is modular with the stem dowel bars for ease of construction. Note: The program does not calculate the heel bar development length inward from the back face of the stem (where the moment is maximum). You can refer to Appendix B for development lengths in concrete, which can be adjusted for the stress level in the heel bars. When detailing footing reinforcing it is important to consider and specify development lengths for both toe and heel bars.

 

Rebar Selections

Use these three entries to pick your toe, heel, and if applicable, key reinforcing. The "Max @" message tells you the maximum spacing allowed for the bar selected.

 

[Footing Width Automatic Design]

Clicking this button will cause the program to iterate footing widths until the soil pressure, overturning stability, and sliding stability ratios are acceptable. You can select either a fixed toe or heel distance, or balance the toe and heel dimensions. You can also select whether the resultant must be within the middle third of the footing. After clicking "Design," the widths required will be displayed.

 

Automatic footing design is not available for Restrained Walls.

 

 

Footing Tab / Key Dimensions and Sliding

 

This screen tells you whether passive soil resistance plus friction resistance is adequate to resist sliding with at least a 1.5 safety factor. If inadequate, you can design a key. If a key is used, the previous footing screen will check whether reinforcing is required by first checking the plain concrete flexural capacity (for computing section modulus, 3" is deducted from the key width per UBC '97). If the key depth to width ratio is less than about 2:1, it's usually adequate.

 

 

clip0380

 

Key Depth

Depth of the key below the bottom of footing. The bottom of the key is used as the lower horizontal plane for determining the size of the passive pressure block from the soil in front of the footing. Adjust this depth so the sliding safety factor is acceptable, but not less than 1.5. A depth greater than three feet or one-half the footing width is not recommended.

 

Key Width

 

Width of the key, measured along the same direction as the footing width. This is usually 12"-14", but generally not less than one-half the key depth so flexural stress in the key is adequate.

 

Key Location

Enter the distance from the front edge of the toe to the beginning of the key. Do not enter a distance greater than the footing width minus key width.

 

Align with Stem

Click this button to set front edge of key aligned with front of stem. If the key is then made the same width as the stem, the stem bars could extend down into the key to achieve development.

 

Soil Over Toe to Neglect for Sliding Resistance

Since the soil over the toe of the footing is usually loose and uncompacted, it may have little or no passive resistance. This entry gives you the option of neglecting any or all of the Height of Soil Over Toe that you had entered in the CRITERIA screen. You can neglect the soil over toe plus the footing thickness, if desired.

 

Footing/Soil Friction Factor

Enter this friction factor here, which is generally provided by the geotechnical engineer. It usually varies from 0.25 to 0.45.

 

% Passive Usable for Sliding Resistance

This may be a stated restriction in the geotechnical report. Enter a value from zero to 100%.

 

% Friction Usable for Sliding Resistance

This may be a stated restriction in the geotechnical report. Enter a value from zero to 100%.

 

Lateral Pressure @ Base of Footing

This is the total lateral force against the stem and footing which causes the wall to slide and which must be resisted. It is the total active pressure on the heel side less the active pressure on the toe side. The latter will be excluded if you choose to delete it on the OPTIONS screen.

 

Less Passive Pressure Force

This uses the allowable passive pressure in pcf and the available depth (soil above toe less height to neglect plus footing thickness) to compute the total passive resistance, again multiplied by the percent usable you selected. Weight due to toe surcharge, if applicable, will also be added. If a key is used, the available passive pressure depth will be to the bottom of the key.

 

Less Friction Force

This is the total vertical reaction multiplied by the friction factor, again multiplied by the percent usable you selected.

 

Added Resisting Force Required

If this is 0.0 lbs., the forces balance, but there may be no safety factor. Watch the Sliding Factor of Safety for an adequate value (usually 1.5). Add a key as required.

 

Added Resisting Force Required for 1.5:1 Safety Factor

This is the additional force required to be resisted by a key to achieve a 1.5 safety factor. If zero, no key is required.

 

Key Reinforcing

If flexural tension is insufficient to resist bending in key, a message will appear indicating reinforcing required. You can vary the width of the key until the message disappears. Or you can manually calculate reinforcing required.

 

Sliding Factor of Safety

This gives you the ratio of passive and friction resistance to the total lateral force. This should be at least 1.5.

 

NOTE : If lateral restraint is provided by an abutting floor slab (by checking the box on the CRITERIA > OPTIONS screen), the sliding factor of safety displays will be deleted, but the "Lateral Force @ Base of Footing" will be displayed for checking restraint adequacy of the slab.

 

 

Stability Tab

 

For Restrained Walls the STABILITY screen will appear differently, summarizing the conditions you have set regarding base fixity and base lateral restraint.

 

clip0395                

 

A banner will display whether a slab is present to resist base sliding (box checked on CRITERIA > OPTIONS screen) and whether fixed or pinned at base, as previously selected on the STEM screen.

 

The reaction at the top restraint will be displayed.

 

The Sliding forces will be displayed, and indicate counteracting active pressure on toe side, if this option was selected on the Options screen.

 

The Moment at Top of footing applied from Stem is the theoretical overturning of the footing due to the reaction at the base of the stem, if the stem is "pinned" at the base. In actual practice the footing will be constructed integrally with the stem (not a true "pin") therefore this displayed overturning moment can be ignored provided the connection between footing and stem is sufficient. You can check the allowable moment at the base of the stem and compare it to the displayed "overturning" moment to verify this.

 

The "Moment used for soil pressure calc," if slab restraint is provided, is the total bearing load times the eccentricity (displayed on Results screen on right). If slab restraint is not provided, and since bottom of stem is considered "pinned," then this is (theoretically) the bottom-of-stem reaction multiplied by the footing depth and may generally be ignored per the preceding paragraph explanation.

 

 

Results & Graphics Tabs

This set of tabs provides the calculated values resulting from your input on the "Data Entry Tabs". Because a recalculation is performed with each data entry, the information on these tabs always reflects the accurate and current results, problem sketch, or stress/deflection diagram.

 

         

Results Tab

 

clip0396

 

Soil Pressure @ Toe and Heel

This is the resulting unfactored soil pressure for both the toe and heel. If the eccentricity is outside the middle third, the heel pressure will show 0.00. (Note: when the resultant is outside the middle-third, the program calculates the toe pressure assuming no "tension" at heel).

 

Allowable Soil Pressure

This is for your reference as input on the Criteria input Screen

 

Total Bearing Load

This is the sum of all vertical forces.

 

Resultant Eccentricity

Distance from center of footing to resultant soil pressure.

 

Eccentricity Within/Outside Middle Third

The resultant is outside the middle third of the footing width if the eccentricity is greater than one-sixth the footing width. (If outside the middle third, the program computes the toe soil pressure assuming no "tension" at heel.)

 

ACI Factored Soil Pressure @ Toe and Heel

ACI or AASHTO load factors are applied to all dead and live loads to determine total vertical load for soil pressure used in calculating footing moments and shears. This load is then applied at the same eccentricity calculated for service load soil pressures to yield the actual factored soil pressures for footing design using ultimate strength design principles. Note that since only factored vertical loads are applied at the non-factored resultant eccentricity, a true 1.7 load factor applied to lateral earth pressure is not used for footing design. If resultant vertical load eccentricity were to be calculated using factored loads, the distance would not truly represent a correct state of stress in the soil. ACI load factors are intended to give conservative results for stress. Calculation of a factored load eccentricity would give soil pressure diagrams that would not always represent the actual soil pressure distribution under the footing, and yield unreasonable results. Factored lateral earth pressure, however, is always used for concrete stem design.

 

Mu Design @ Toe/Heel

These are the factored (by 1.4) moments at face of stem for toe and heel moments. Since neither can be greater than the stem base moment (factored if concrete stem), the latter may govern. These moments will be reduced if you choose to neglect the upward soil pressure on the Criteria > Options tab.

 

A message will indicate which controls.

 

Shear @ Toe and Heel

The actual shear is calculated from the one-way action in the footing at a distance "d" (footing thickness - rebar cover) from the toe side of the bottom stem section, and at the face of the stem on the heel side. If "d" is greater than the projecting toe or heel length, then the one-way shear is zero.

 

Allowable Footing Shear

The allowable unit shear equals (0.85 * 2 *_bm146½).

 

Construction Sketch Tab

This tab provides a sketch of the beam with loads and resulting values shown. Using the [Print Sketch] button will print the sketch in large scale on a single sheet of paper.

 

clip0397

 

Wall Loading Diagram Tab

This tab provides a sketch of the wall and it's applied loads. Using the [Print Sketch] button will print the sketch in large scale on a single sheet of paper.

 

clip0398

 

 

 

Sample Printout

 

RESTWALL_PRT_1

 

RESTWALL_PRT_2